Silent type generator set is on the basis of well-catalogued diesel generator to increase the static sound box, and the whole diesel generating set enclosed, also in the case of adhesive on the wall insulation flame retardant material, this makes a lot of noise reducing diesel generating sets, but also the function of waterproof, general use or real estate and hotels and other places in the downtown area, Need to reduce the noise to a certain extent, the usual standard is 7 meters away noise is less than or equal to 75 decibels, then silent diesel generator daily needs to maintain?


The advantages of the silent generator set are that the appearance is integrated, so it is more beautiful, and there is no need to worry about the impact of rain and snow on the internal diesel generator, and it can reduce some noise, but the disadvantage is that if the maintenance is not good, it is easy to cause high temperature, resulting in the damage of the diesel generator. In addition, the base part of the silent generator set has a fuel tank, so it is necessary to pay attention to no damage when lifting and moving. When refueling, it should be paid attention to that the diesel back needs to be static for more than 12 hours for filtering, so as to try to make less impurities in the oil tank to block the oil pipe, to prevent insufficient oil supply.


Complete basic appearance inspection monthly


1. Keep the generator set and its surroundings generally clean. Make sure there are no rats in an enclosed room to prevent wires and cables from being chewed up by rats.


The unit cannot run while the oil is being checked. If the generator is already running, wait 10 minutes and check the oil level to ensure that the oil level is sufficient for use but not overflowing.


2. Ensure that there is an adequate level of coolant inspection


Diesel set, check oil level and oil/water separator. Add condensate from the separator. Check fuel lines for leaks or visible damage. Check for corrosion, damage, or terminals. Check and clean corrosive batteries.


3. In addition to monthly inspection; The coolant thermal protection level is also checked every six months. Use the appropriate type of use, at the same time, check the driving belt tension condition.


Replacement of engine oil and filter is required for annual maintenance of backup generator sets. Replace the air filter, fuel filter.


4. Two commonly neglected parts need to be checked or replaced once a year: the generator itself and the transfer switch:


Alternators usually require only a simple appearance inspection. Whether there is dirt, dirt can prevent heat transfer and affect the cooling effect. So according to the manufacturer's recommendations to clean the winding every year. Changeover switch check requires a thorough annual inspection by turning off all power switches first.


Daily technical maintenance


(a) Wipe the dust and oil in each part of the unit, check and eliminate the phenomena of oil leakage, water leakage and air leakage in each part.


(b) Check whether the connecting bolts and nuts of each part are loose after operation. Especially the fastening of the footings.


(c) Check the oil condition and quality of the oil pan memory before and after operation. If the quality deteriorates, there are metal shavings in the oil or sudden increase or decrease in oil brightness, the reason should be checked, and timely replenishment and replacement of new oil.


(d) Check the oil plane of the injection pump governor before operation, and it should reach the line mark of the oil ruler.


(e) In the equipment room with dusty environment, clean the air filter after a long time of operation.


(f) Clean oil and water marks of electrical equipment before and after operation, and check whether the joints are firm.


(g) Before operation, check whether the conveyor belt is good, whether the belt joint is firm, and whether the tightness is appropriate.


(h) Check the amount of oil in the diesel tank before and after long-term operation, and check whether all parts of the fuel system and tubing joints are in good condition.


2018120501.jpg


Jiangsu Meiao Power Technology Co., Ltd. is an important manufacturer of diesel generators. The company mainly manufactures and sells diesel generator sets with power of 3-3000kW, mobile power station of 24-600kW, Marine emergency diesel generator set of 24-800kW, gas generator set, heavy oil generator set and all kinds of imported series, special series (trailer, static speaker, mobile lighthouse, container, etc.) diesel generator At the same time, we are engaged in generator set maintenance and after-sale service of generator set accessories.